z ■<

o ■I io i ■ CD

I INDOOR AIR QUALITY ANALYSIS ■D o c o CT o o Project: Newmark & Co. Real Estate, Inc. CTSI Project #.• NY-442-01 Date: November 8, 2001 o' o ■D 00 100 Gold Street o co 3. 00 03

LOCATION TEMPERATURE RELATIVE CO2 (PPM) CO (PPM) TOTAL O o HUMIDITY PARTICULATE o (’F) c (RH%) LEVELS 3 CD

Standard = Standard = Standard = Standard = Standard= 68-74°F 30-50% 1.nW PPM 9.0 PPM 0.015 mg/m^ Outside 59.0 39.5 366 1.5 0.030 9'"Fl.Section-A 71.2 29.4 551 1.1 <0.001 9"’Fl. Section-M 72.4 28.1 592 1.0 <0.001 9“’ Fl. Section-Z 72.6 28.3 623 1.0 <0.001 9* Fl. Section-0 73.6 26.7 504 1.1 <0.001 8^Fl.Section-A 74.8 26.3 630 1.1 <0.001 8*^ Fl. Section-M 75.3 26.3 607 1.1 <0.001 8*^ Fl. Section-Z 75.1 26,9 678 1.1 <0.001 8^" Fl. Section-0 74.9 26.5 595 1.1 <0.001 7^Fl.Section-A 75.9 25.5 558 1.1 <0.001 7"’ Fl. Section-M 76.0 . 26.0 640 1.1 <0.001 7“* Fl. Section-Z 76.6 25.9 622 1.1 <0.001 7*^ Fl. Section-0 76.5 25.3 583 1.2 <0.001 6^ Fl. Section-A 76.3 25.5 554 1.2 <0.001 6*^ Fl. Section-M 76.0 26.0 602 1.1 <0.001 6^ Fl. Section-Z 76.0 26.6 678 1.2 <0.001 6“’Fl. Section-0 75.7 26.1 615 1.2 <0.001 iiH o °F = degrees Fahrenheit CO = Carbon monoxide CO2 = Carbon dioxide PPM = Parts Per Million H K RH = Relative humidity ND = Non Detected I

I o o I s o o o on

o 1

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000301898Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000302299

Indoor air quality analysis documentation for NY-442-01 project at 100 [name].

Similar indexed content

NYC-WTC_000302298

Indoor air quality analysis data for NY-442-01 project; date shown.

Similar indexed content

Compare copies and versions →