NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 2 pages

NYC-WTC_000301867

Label derived from the City's folder field. The City does not supply document titles.NYC-WTC_000301867–000301868
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

z z ■<

o o

i 1^ to

1 INDOOR AIR QUALITY ANALYSIS o o o Ca5 Project: Newmark & Co. Real Estate, Inc. CTSI Project #.-NY-442-01 Date: October 25, 2001 I O 00 100 Gold Street O>

■ LOCATION TEMPERATURE (“F)

Standard - RELATIVE HUMIDITY (RH%)

Standard = CO2 (PPM)

Standard = CO (PPM)

Standard = TOTAL VOC’S

Standard = Varies TOTAL PARTICULATE LEVELS

Standard= 5 68-74°F 30-50% 1,000 PPM 9.0 PPM per specific 0.015 mg/m’ parameter Outside 73.8 37.4 339 1.4 ND 0.400 O'** Fl. Section-A 75.5 43.7 602 1.3 ND 0.001 6^' Fl. Section-M 74.4 43.4 615 1.2 ND 0.001 6‘'’ Fl. Section-Z 74.1 46.0 673 1.3 ND 0.02 6*^ Fl. Section-0 72.2 45.4 558 1.3 ND 0.001 8^ Fl. Section-A 73.2 44.8 556 1.2 ND 0.002 8^^ Fl. Section-M 73.5 44.5 676 1.2 ND 0.001 8‘'' Fl. Section-Z 73.7 46.3 711 1.2 ND 0.001 8*^ Fl. Section-0 73.3 46.2 625 1.2 ND 0.001 7^' Fl. Section-A 74.8 41.5 580 1.2 ND 0.004 7*^ Fl. Section-M 73.9 42.1 594 1.2 ND 0.005 7^ Fl. Section-Z 74.4 43.6 644 1.2 ND 0.003 7^' Fl. Section-0 74.3 43.5 631 1.2 ND 0.003 5^ Fl. Section-A 74.2 39.7 534 1.1 ND 0^ 5*^ Fl. Section-M 74.2 38.9 539 1.1 ND 0.003 5^' Fl. Section-Z 72.8 43.3 587 1.2 ND 0.002 5“’ Fl. Section-0 72.8 43.1 573 1.1 ND 0.003 o H k; "F = degrees Fahrenheit CO = Carbon monoxideCO2 = Carbon dioxide PPM = Parts Per Million I to RH = Relative humidity ND = Non Detected s O o o I o o co co

o ri bJ (JI

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000301867Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →