IAQ measurements report, High School for Leadership

Machine-extracted title · confidence 41%

Indoor air quality measurements at the referenced HS, BOE request.

NYC-WTC_000296893–000296896
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 30, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894~) ATC Project No. 15-19125-0290 TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Forty-three (43) of the indoor measurements for temperature were below and eighty-five (85) were Within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. One hundred and seven (107) of the indoor measurements for relative humidity were below and twenty-one (21) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest measurement (1346 ppm) was collected in room 905 at 10:30 AM with 34 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration. 5. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 290 or 212.

Sincerely, TC ASSOCIA TES INC.

ArKel Javaly James R. Cohn, CIH, CSr Senior Pro^jeict Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_003086806

NYC-WTC_000296896

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000296896Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000296762

ATC IAQ measurements report for HS for Leadership & [name], Apr 15, 2002.

Similar indexed content

NYC-WTC_000410943

IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.

Similar indexed content

NYC-WTC_000410947

Follow-up IAQ report for the referenced NYC BOE project, June 2002.

Similar indexed content

Compare copies and versions →