Indoor air quality field report, HS for Leadership & [name],

Machine-extracted title · confidence 28%

ATC IAQ measurements at 90 Trinity Place; report dated Apr 17, 2002; project 15-19125-0290.

NYC-WTC_000296785–000296788
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 18, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment: • No smoke odor was detected in the building; FINDINGS

Based on the real-time measurements, the following findings are presented:

2. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines. 3. All of the indoor measurements for temperature were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 4. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 5. AU of the indoor and outdoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and seventy six (76) measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor Respirable particulate concentrations ranged from 42 pg/m^ to 47 pg/m3 with an average of 45 pg/m^.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext # 211 or 212.

Sincerely, Reviewed by: ATC ASSOCIATES INC.

Prasad Doddapaneni' James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_003086655

NYC-WTC_000296788

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000296788Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394783

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000410951

BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.

Similar indexed content

NYC-WTC_000410943

IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.

Similar indexed content

Compare copies and versions →