Mr. Bernard P. Orlan April 16, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Two (2) indoor measurements for temperature were below, one hundred nineteen (119) measurements were above, and five (5) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Eight (8) of the indoor measurements for relative humidity were above, one hundred and eighteen (118) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4, Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading was measured in the basement hallway at 2:55 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration, 5. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 p,g/m3 24-hour average concentration of particulate matter 2,5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext # 211 or 212.

Sincerely, Reviewed by: J TC ASSOCIA TES INE

tel Javi James R. Cohn, CIH, CSP Senior Prbifect Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_003086620

NYC-WTC_000296765

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000296765Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394764

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000296893

Indoor air quality measurements at the referenced HS, BOE request.

Similar indexed content

NYC-WTC_000394734

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

Compare copies and versions →