Mr. Bernard P. Orlan April 16, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and thirty-seven (137) sets of real-time environmental measurements consisting of one hundred and twenty-six (126) in the school building and eleven (11) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 7.15 A.M, and concluded after 2:55 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 59.2 °F to 80 °F. Two (2) indoor measurements for temperature were below, one hundred nineteen (119) measurements were above, and five (5) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 67.7 °F to 79.5 °F.
Relative Humidity
The relative humidity indoors ranged from 33.5 percent to 62.9 percent. Eight (8) of the indoor measurements for relative humidity were above, one hundred and eighteen (118) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 42.1 to 64.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 132 ppm to 1529 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 742 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1442 ppm (background level + 700 ppm). The highest reading was measured in the basement hallway at 2:55 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations are 2 ppm for all readings.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 6 (J,g/m3 to 21 pg/m3 with an average 14 pg/m^- All of the indoor and outdoor measurements for FM2.5 were below the NPAAQS of 65 ug/m? 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 11 pg/m^ to 51 pg/m^ with an average of 13 pg/m^. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_003086619
NYC-WTC_000296764
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394764
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394886
Indoor air quality measurements collected at the referenced school in April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370422
Indoor air quality measurements collected March 6, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394768
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292020
ATC IAQ measurements collected June 24, 2002 for the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000394764
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296754
ATC memo with IAQ measurements at HS for Leadership & [name], Apr 11, 2002, BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296758
ATC IAQ measurements report for HS for Leadership & [name], Apr 12, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370524
Indoor air quality measurements collected March 20, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
NYC-WTC_000394886
Indoor air quality measurements collected at the referenced school in April 2002.
Similar indexed content
NYC-WTC_000296781
ATC IAQ FIELD REPORT for 90 Trinity Place; measurements collected Apr 16, 2002, project 15-19125-0290.
Similar indexed content
Indoor air quality measurements at the referenced HS, BOE request.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content