Mr. Bernard P. Orlan . April 9, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M8Q4) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:12 A.M. and concluded after 3:57 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 68.1 °F to 75.1 °F. One hundred and twenty-five (125) indoor measurements for temperature were within and three (3) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 52.5 °F to 56.8 °F.
Relative Humidity
The relative humidity indoors ranged from 27.1 percent to 39.6 percent. Sixty-eight (68) of the indoor measurements for relative humidity were below and sixty (60) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 35 to 41.6 percent.
CarhonDioxideConcentration
Carbon dioxide concentrations indoors ranged from 437 ppm to 1436 ppm. Two (2) of the indoor measurements for CO? were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 484 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1184 ppm (background level -1- 700 ppm). The highest reading was measured in the gym at 10:59 AM with 27 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm- 4 ppm.
Respirable Particulates (PM2^^)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 24 pg/m^ with an average 9 pg/m^- All of the indoor measurements for PM2,5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 29 pg/m^ to 84 pg/m^ with an average of 54 pg/m3. Four (4) of the outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average
CITY_21MC100_003086542
NYC-WTC_000296751
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394729
Indoor air quality report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370524
Indoor air quality measurements collected March 20, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370529
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370557
ATC reports IAQ measurements taken March 26, 2002 at High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211863
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 27, 2002, to evaluate possible contamination.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370440
Indoor air quality measurements collected March 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370473
March 11, 2002 IAQ measurements report for the BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296754
ATC memo with IAQ measurements at HS for Leadership & [name], Apr 11, 2002, BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394756
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370411
ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000394729
Indoor air quality report for High School for Leadership & [name], Apr 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260521
ATC IAQ measurements collected June 3, 2002 at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296754
ATC memo with IAQ measurements at HS for Leadership & [name], Apr 11, 2002, BOE request.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370557
ATC reports IAQ measurements taken March 26, 2002 at High School for Leadership & [name].
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399294
Indoor air quality measurements collected May 9, 2002, for the High School for Leadership & [name].
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality report for High School for Leadership & [name], Apr 2002.
Similar indexed content
Indoor air quality measurements collected March 20, 2002 at the referenced school.
Similar indexed content
Indoor air quality measurements collected March 21, 2002 at the referenced school.
Similar indexed content
ATC reports IAQ measurements taken March 26, 2002 at High School for Leadership & [name].
Similar indexed content
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 27, 2002, to evaluate possible contamination.
Similar indexed content