Mr. Bernard P. Orlan October 11, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant H.S. (M477) ATCJYgiectJYoJTJ.912^^
SAMPLING RESULTS
Real-Time Environmental Measurements
ATC collected one hundred-two (102) sets of real-time environmental measurements consisting of one hundred (100) in the school building and two (2) outdoors. These results are described below. Field data sheets are found in Attachment 1. I
Temperature
Indoor dry bulb temperature measurements ranged from 69.9 °F to 75.8 °F. Measurements were within the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 62.1 to 70.5°F.
Re/ative Humidity r
The relative humidity indoors ranged from 38.9 percent to 49.5 percent. All measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 3 7.5 to 50.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 404 ppm to 1690 ppm. Eleven (11) COo measurements were at or above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration range was 338 to 367 ppm. Therefore, the acceptable level of CO2 at this location was 1038 ppm (background level + 700 ppm). Thirteen measurements were within 10% of the 1038 ppm level. The highest level measured (1690 ppm) was in a fully occupied classroom (Room 737). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COn indoors is occupant respiration.
CarbonMonoHdeConcen^tion
Carbon monoxide concentrations indoors were 0 - 5ppm for all readings. These concentrations were below the NPAAQS/.ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 - 1 ppm.
Respirable Particulates
Respirable particulate concentrations indoors ranged between 12 pg/m^ and 55 pg/m^. Only one (1) concentration was above the NPAAQS/ASHRAE guideline of 50 pg/m-’ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The sample with concentration of respirable particulates above the NPAAQS/ASHRAE guideline of 50 pg/m3 was collected from room #351. The outdoor respirable particulate concentration range was 16 to 18 pg/nP.
CITY_21MC100_003081558
NYC-WTC_000292856
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000271073
Indoor air quality assessment report for Stuyvesant High School dated Oct 2001.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271099
Indoor air quality assessment results for Stuyvesant HS dated Oct 12, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292880
Cover letter presenting IAQ field report for Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188511
Letter from ATC Associates providing an indoor air quality assessment report for Stuyvesant High School dated October 12, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271114
Indoor air quality assessment conducted at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292885
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311732
Indoor air quality assessment conducted October 12, 2001 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311704
Indoor air quality assessment conducted on October 10, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271057
Letter discussing Stuyvesant High School project and related communications.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000311704
Indoor air quality assessment conducted on October 10, 2001 at Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311687
Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292880
Cover letter presenting IAQ field report for Stuyvesant HS.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314680
IAQ measurements report for PS 234M by ATC.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188511
Letter from ATC Associates providing an indoor air quality assessment report for Stuyvesant High School dated October 12, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000271073
Indoor air quality assessment report for Stuyvesant High School dated Oct 2001.
Similar indexed content
NYC-WTC_000271099
Indoor air quality assessment results for Stuyvesant HS dated Oct 12, 2001.
Similar indexed content
NYC-WTC_000292880
Cover letter presenting IAQ field report for Stuyvesant HS.
Similar indexed content
NYC-WTC_000188511
Letter from ATC Associates providing an indoor air quality assessment report for Stuyvesant High School dated October 12, 2001.
Similar indexed content
NYC-WTC_000271114
Indoor air quality assessment conducted at Stuyvesant High School.
Similar indexed content