Mr. Bernard P. Orlan May 13, 2002 Indoor Air Quality Assessment Page 3 H.S, for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 71.9 °F to 78.9 °F. Thirty-three (33) of the indoor measurements for temperature were below and ninety-five (95) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season . The outdoor temperature ranged from 74.9 to 79.9 °F.
Relative Humidity
The relative humidity indoors ranged from 36.2 percent to 51.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 27.1 to 42.1 percent.
Catbon Dioxide Cjmcentraiian
Carbon dioxide concentrations indoors ranged from 416 ppm to 1256 ppm. One (1) of the indoor measurements for CO, were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO, concentration was 548 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1248 ppm (background level + 700 ppm). The highest measurement (1256 ppm) was measured in Room 1015 around 11:10 AM. with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 to 2 ppm.
Respirable Particulates (PM2 J
Respirable particulate concentrations* indoors ranged between 4 pg/m’ to 23 pg/m’ with an average 15 pg/m^' All the indoor measurements for PM15 were within the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m’ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 33 pg/m’to 38 pg/ra’ with an average of 35 pg/m’.
CITY_21MC100_003079366
NYC-WTC_000291775
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399312
Indoor air quality measurements collected May 10, 2002, for the High School for Leadership & [name].
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260325
ATC report of IAQ measurements taken May 10, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292000
ATC IAQ measurements collected June 14, 2002 for the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291976
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000399312
Indoor air quality measurements collected May 10, 2002, for the High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399420
Indoor air quality measurements collected May 20, 2002, for the High School for Leadership & [name].
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291705
Indoor air quality report for High School for Leadership & [name], May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000399312
Indoor air quality measurements collected May 10, 2002, for the High School for Leadership & [name].
Similar indexed content
NYC-WTC_000260325
ATC report of IAQ measurements taken May 10, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
Similar indexed content
ATC IAQ measurements collected June 14, 2002 for the referenced school.
Similar indexed content
NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
Similar indexed content