Mr. Bernard P. Orlan February 12. 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Proiect No. 15-19125-0289
Real-Time En vironm ental Measurements
ATC collected forty' (40) sets of real-time environmental measurements consisting of thirty (30) Lorn inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below'.
Field data sheets are found in Attachment 1. Readings began at 11:00 A.M, and concluded at approximately 3:30 P.M.
'remperatuft'
Indoor dry bulb temperature measurements ranged from 71.8°F to 77.6”F. Ten (10) of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 35.1 to 37.8‘T.
Rclaiive Humidity
The relative humidity’ indoor s ranged from 17.0 to 25.7 percent. All of the measurement.s w ere below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity' measurements ranged from 27.3 to 29.3 percent.
Ciirhon Diotdde C'onceniralum
Carbon dioxide concentrations indoors ranged from 520 ppm to 1126 ppm. All of the CO2 measurements were within the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The; maximum outdoor (background) CO2 concentration was 486 ppm. Therefore, the maximum acceptable level of CO2 at thi.s location was 1186 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
C iu rbo nMo k o.yddeCon^'ntralion
(kirbon monoxide concentrations indoors w'ere 0 ppms for the interior readings. These concentrations were below' the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 to 1 ppm.
Ri’spirable Particulates (PM^, 5)
Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 16 pg/m^. None of the measurements were above the NPAA.QS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2 5 concentration for the entire school building was approximately 9 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals I children. The outdoor respirable particulate concentration measurements ranged from 3 to 14 pg/m^ with an average of 8 pg/m^.
CITY_21MC100_002954119
NYC-WTC_000289360
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000289398
Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253631
BOE-requested IAQ measurements at the NYC school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374676
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375489
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374708
ATC IAQ measurements at P.S. 150M for BOE air quality assessment, April 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300752
ATC reports basic IAQ parameters for PS 150M, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178791
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on June 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410467
IAQ measurements collected Feb 15, 2002 at PS 150M for BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000398145
IAQ measurements at a NYC school (P.S. 150M) for May 3, 2002, by ATC Associates.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253631
BOE-requested IAQ measurements at the NYC school prior to re-occupancy.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000202319
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Board of Education school to evaluate building conditions.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392633
ATC IAQ measurements report dated April 16, 2002 for PS 89M BOE evaluation.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313339
ATC IAQ memo detailing measurements and scope of work at PS 89M.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000187689
Cover letter from ATC Associates submitting an indoor air quality assessment report for PS150M collected on March 5, 2002.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000289398
Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.
Similar indexed content
NYC-WTC_000253631
BOE-requested IAQ measurements at the NYC school prior to re-occupancy.
Similar indexed content
NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
Similar indexed content
NYC-WTC_000374676
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
Similar indexed content
NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
Similar indexed content