NYC-WTC_000289398
Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements collected February 11, 2002 for PS 150M.
NYC-WTC_000289358–000289361OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 12, 2002 Indoor Air C)uality Assessment Page 2 P. S. 150M ATCProiectJNqJ5J9125;02^
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not -represent conditions found at other times. The infonnation presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
. -Ta.... . Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHKAE55 Winter: 68-75 °F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002954118
NYC-WTC_000289359
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000289398
Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253631
BOE-requested IAQ measurements at the NYC school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374676
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375489
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374708
ATC IAQ measurements at P.S. 150M for BOE air quality assessment, April 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300752
ATC reports basic IAQ parameters for PS 150M, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178791
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on June 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410467
IAQ measurements collected Feb 15, 2002 at PS 150M for BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300705
ATC IAQ measurements at PS 150M before occupancy, Feb 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410559
Report of IAQ measurements at a NYC school building prior to re-occupancy, March 7, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382619
Report of indoor air quality measurements at P.S. 89M requested before re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253699
IAQ data collection at PS150 M for school building air quality assessment.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249692
Indoor air quality measurements at PS 150M prior to re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000289398
Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.
Similar indexed content
NYC-WTC_000253631
BOE-requested IAQ measurements at the NYC school prior to re-occupancy.
Similar indexed content
NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
Similar indexed content
NYC-WTC_000374676
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
Similar indexed content
NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
Similar indexed content