Gypsum
Before Cleaning Samples - There were four pre-cleaning wipe samples collected. The
results indicate gypsum was not detected above the detection limit of 40 mg/m^.
Post P' Cleaning Samples, Test 4A - There were two air and four wipe samples
collected. Sampling results indicate that gypsum was not detected in air above the
detection limit range of 0.008 mg/m^ to 0.017 mg/m^ or in the wipe samples above
the detection limit of 10 rng nr.
Post Cleaning Samples, Test 4B - There were two air and four wipe samples
collected. Sampling results indicate that gypsum was detected in air at concentrations
of 0.011 mg/m’ and 0.014 mg/m\ Gypsum was not detected in the wipe samples
above the detection limit of 10 mg/m^.
Post J" Cleaning Samples, Test 4C - There were two air samples collected. Sampling
results indicate that gypsum was detected in air above the detection limit with the
results of 0.009 mg/m^ to 0.012 mg/m\
Lead
Before Cleaning Samples - There were four micro vacuum samples and four wipe
samples collected. The results indicate that lead was detected in all of the micro
vacuum samples and wipe samples collected. Three of the four micro vacuum results
exceeded the comparison value of 25 pg/ft^, ranging from 7.22 pg/ft' tol81 pg/ft^.
Wipe sample concentrations exceeded the primary numeric criterion of 25 pg/lV in all
of the samples ranging in concentrations from 74.7 pg/ff to 433 pg/fV.
Post P' Cleaning Samples, Test 4A - There were two air samples, four micro vacuum
samples, and four wipe samples collected after the first cleaning. The two air samples
were below the numeric criterion of 1 pg/m\ The results of the micro vacuum and
wipe samples show that, while all of the micro vacuum and two of the wipes samples
were below the comparison value or primary numeric criterion, the remaining two
wipe samples exceeded the primary numeric criterion with concentrations of 64.5
pg/tf and 146 pg/ff.
Post Cleaning Samples, Test 4B - There were two air samples and four wipe
samples collected. The two air samples were below the numeric criteria of 1 pg/m\
Two of the four wipe samples exceeded the primary numeric criterion at
concentrations of 147 pg/ft" and 556 pg/ft\
Post J" Cleaning Samples, Test 4C - There were two air samples and four micro
vacuum samples collected. The two air samples both exceeded the numeric criterion
91