Post P' Cleaning Samples - There were no post-first cleaning samples collected.
Unit 4A - This unit is located on the fourth floor. It is a 1,368 sq. ft. open loft facing Cedar Street.
No windows were blown-in and there was minimal dust accumulation in the dwelling with the
exception of the baseboard heating units, which contained visible dust. The unit has hardwood
floors and all the tenant’s personal items were removed prior to the cleanup.
Cleaning method - This unit was cleaned using test method 2A. Test method 2A used a
Craftsman shop vacuum and Eureka upright vacuum with a HEPA filter for vacuuming the
floors and other surfaces. There were no air filtration devices (AFDs) used during the
cleaning process. In addition, all horizontal surfaces were wet wiped. This cleaning method
was used for each cleaning event.
Numeric Criteria - This unit met the numeric criteria listed in Table I for each compound
after being cleaned twice.
Asbestos
Before Cleaning Samples - Pre-cleaning micro vacuum and wipe samples were collected for
asbestos. These samples indicate that asbestos was present in the unit prior to cleaning. All
three micro vacuum samples detected chrysotile above the detection limit. Three of the four
wipe samples were below the detection limit; however, two of these samples had chrysotile
detected. The fourth wipe sample was above the detection limit.
Post P' Cleaning - There were post-cleaning air, micro vacuum, and wipe samples collected.
The three air samples were analyzed using PCM, TEM AHERA, and TEM PCMe. The
PCM, TEM AHERA and TEM PCMe analyses could not be conducted due to overloading of
particulate material. Due to not having valid asbestos air results, a second cleaning was
conducted.
The results for the three micro vacuum samples indicate that asbestos was present at levels
similar to or higher than those observed before cleaning. One of the samples was identified
as non-detect, although asbestos was present below the detection limit.
The results for the five wipe samples that were collected indicate that asbestos was present in
all five samples, although two samples were below the detection limit. The concentrations
observed were similar to or higher than the pre-cleaning samples.
Post 2'“^ Cleaning - There were three asbestos air samples collected after the second cleaning.
The samples were analyzed for PCM, TEM AHERA, and TEM PCMe. The PCM results
could not be obtained due to the filter being overloaded with particulate material. The TEM
AHERA results for each sample were below the detection limit and below the secondary
numeric criterion of 0.022 S/cc. The TEM PCMe results were ail below the primary numeric
56