the detection limit of 4.65 ug/fF. The wall samples cannot be used due to the
pre- and post-samples being below the detection limit, however the results for
the counter top and bare floor suggest that water is effective at reducing lead
concentrations.
The contradictory nature and variable results of the tests discussed above, as
well as the small sample size, prohibit any conclusions to be made about the
effectiveness of using only water to remove lead.
The Heating Ventilation Air Conditioning (HVAC) system cleanings were effective in
removing significant amounts of dust and associated contaminants in the dust.
• Cleaning was conducted by professionals using equipment and techniques
common to the industry that included HEPA filtered vacuums, air whips, air
washing and soap and water washes.
• Results from the Food Exchange - Pre-clean and post-clean wipe samples
were collected from the interior of the duct work located at the Liberty Street
and Cedar Street entrances. The samples were analyzed for asbestos, lead,
MMVF and silica. Comparison of the pre-cleaning data to the post cleaning
data indicated reductions of the analytes by an order of magnitude. Asbestos
was reduced from 302,504S/cm^ to <30,250S/cm\ lead from l,310ug/m' to
159ug/m3 (avg), MMVF 11,732S/1 to <57.3 S/1 and Silica 313 mg/nr to .07
mg/m2 (r). Air samples collected for asbestos, lead, MMVF and silica were
all below the numeric criteria.
• Results from the Lemongrass Restaurant - Pre-clean and post-clean wipe
samples were collected from the interior of the duct work located at the
Liberty Street entrance and from the air handler at Cedar Street entrance. The
samples were analyzed for asbestos, lead, MMVF and silica. Comparison of
the pre-cleaning data to the post cleaning data indicated reductions of the
analytes was significant. Asbestos was reduced from <30,250S/cnf to
<12,100S/cm^ lead from 10,700ug/m^ to 95.95ug/m’ (avg), MMVF <57.3
S/1 to < 57.3 and Silica 718 mg/nr to <20 mg/m’. Air samples collected for
asbestos, lead, MMVF and silica analysis were all below the numeric criteria.