INTERNAL REVIEW DRAFT

the detection limit of 4.65 ug/fF. The wall samples cannot be used due to the pre- and post-samples being below the detection limit, however the results for the counter top and bare floor suggest that water is effective at reducing lead concentrations. The contradictory nature and variable results of the tests discussed above, as well as the small sample size, prohibit any conclusions to be made about the effectiveness of using only water to remove lead.

The Heating Ventilation Air Conditioning (HVAC) system cleanings were effective in removing significant amounts of dust and associated contaminants in the dust. • Cleaning was conducted by professionals using equipment and techniques common to the industry that included HEPA filtered vacuums, air whips, air washing and soap and water washes. • Results from the Food Exchange - Pre-clean and post-clean wipe samples were collected from the interior of the duct work located at the Liberty Street and Cedar Street entrances. The samples were analyzed for asbestos, lead, MMVF and silica. Comparison of the pre-cleaning data to the post cleaning data indicated reductions of the analytes by an order of magnitude. Asbestos was reduced from 302,504S/cm^ to <30,250S/cm\ lead from l,310ug/m' to 159ug/m3 (avg), MMVF 11,732S/1 to <57.3 S/1 and Silica 313 mg/nr to .07 mg/m2 (r). Air samples collected for asbestos, lead, MMVF and silica were all below the numeric criteria. • Results from the Lemongrass Restaurant - Pre-clean and post-clean wipe samples were collected from the interior of the duct work located at the Liberty Street entrance and from the air handler at Cedar Street entrance. The samples were analyzed for asbestos, lead, MMVF and silica. Comparison of the pre-cleaning data to the post cleaning data indicated reductions of the analytes was significant. Asbestos was reduced from <30,250S/cnf to <12,100S/cm^ lead from 10,700ug/m^ to 95.95ug/m’ (avg), MMVF <57.3 S/1 to < 57.3 and Silica 718 mg/nr to <20 mg/m’. Air samples collected for asbestos, lead, MMVF and silica analysis were all below the numeric criteria.

119

CITY_21MC100_004205075

NYC-WTC_000276771

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000276771Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000243565

EIA report for Law Department project at 100 Church Street by TRC.

Similar indexed content

Compare copies and versions →