Total Dust
Before Cleaning Samples - There were no pre-cleaning samples collected.
Post P' Cleaning Samples - There were no samples collected after the first cleaning.
HVAC System - There was one micro vacuum sample and two wipe samples
collected. The results for the micro vacuum sample indicate that dust was present
below the numeric criterion of 0.50 mg/cm^ for this project. This value is lower than
the numeric criterion set by the NADCA. EPA did not request analysis of the two
wipe samples.
Liberty Street Stairwell - The stairwell consisted of cast concrete steps/landings, sheetrock
walls and ceiling. All surfaces covered with gloss paint.
Cleaning method - This area was cleaned using test method 4A and test method 4B.
Test method 4A used an industrial HEPA filtered vacuum and an AFD. Test method
4B consisted of a soap and water wet wipe of all horizontal and vertical surfaces.
Numeric Criteria - This area did not meet the numeric criterion for silica listed in
Table 1. Due to a delay in receiving analytical result, this exceedance was not
identified until after the close of the study. However, the only elevated sampling
result for airborne silica was obtained from the Liberty Street staircase. This result is
inconsistent with the other 53 samples taken throughout apartments and common
spaces in the building. Those results were all reported to be below detection limits.
Consequently, the presence of a single elevated sample result in a low occupancy area
of the building is not indicative of a health hazard.
Asbestos
Before Cleaning Samples - There were no before cleaning samples collected.
Post P' Cleaning Samples - Two post-cleaning air samples were collected for
asbestos. These samples were analyzed for PCM, TEM AHERA, and TEM PCMe.
The PCM results were all below the secondary numeric criterion of 0.01 f/cc. The
TEM AHERA results indicate that one was below the detection limit and one was at
the detection limit. Both samples were below the secondary numeric criterion of
0.022 S/cc. The TEM PCMe results indicate that one was below the detection limit
and one was at the detection limit. Both samples were below the primary numeric
criterion of 0.0009 S/cc.