NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ memo, Stuyvesant High School, Dec 2001

Machine-extracted title · confidence 28%

December 21, 2001 IAQ measurements at Stuyvesant High School for BOE.

NYC-WTC_000274049–000274052
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan December 24, 2001 Indoor Air Quality Assessment Page 3 Stuwesant High School (M477) ATCProiectNoA5-]912S0246

Temperature

Indoor dry bulb temperature measurements ranged from 69.1 °F to 78.0 °F. Ten (10) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 9^^, 7th , gth ,5th ^^d 4th floors. The outdoor temperature range was 45.5 to 46.6 °F.

Jielative Humidity

The relative humidity indoors ranged from 15.7 percent to 30.9 percent. One hundred thirteen (113) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 23.2 to 28.8 percent.

Carbon Dioxide Concentratien

Carbon dioxide concentrations indoors ranged from 469 ppm to 1830 ppm. Thirteen (13) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 430 ppm and 460 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1160 ppm (background level + 700 ppm). The highest reading, 1830 ppm, was in Room 753. Rooms with CO2 levels above the recommended maximum were found on 9^^, gth, 7th, gth, 5th, 4th and 3rd floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM2_§)

Respirable particulate concentrations* indoors ranged between 3 gg/m^ to 14 gg/m^. All measurements were below the NPAAQS of 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 12 and 26 gg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, 6th and 7th floors (See Attachment). The PM2.5 concentration range for those rooms was 3 - 6 pg/m3 with an average of approximately 4 gg/m^. The PM2.5 concentration range for the other rooms was 3-14 pg/m^ with an average of approximately 6 gg/m^. The average Phl2.5 concentration for the entire school building was approximately 5 gg/mA

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_003107125

NYC-WTC_000274051

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000274051Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000273926

IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.

Similar indexed content

NYC-WTC_000255612

ATC report of IAQ measurements at Stuyvesant High School for December 2001.

Similar indexed content

Compare copies and versions →