NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

TEM analysis, NSHA-EB&R-10/8-06, Oct 2001

Machine-extracted title · confidence 39%

TEM analysis data for NSHA EB&R-10/8-06, Oct 2001.

NYC-WTC_000270294
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

4 ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/08/01

ASBESTOS FIBER j\NALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Rule, ERA Federal Register (40 CFR, Part 753). Vol. 52, No. 210, October 30, 1987

Sample Identification Analysis Parameters

Project/Site: New Stuyvesant H.S., 34 5 Chambers St., NY, NY TEM Sample No.: 5639 - 60571 Exterior of Building & Roof D«3te Received: 10/08/01 Grid Openings Analyzed:__ 4

Project Sample No.: NSHA-EB&R-10/8-06 Average Grid Opening: 106.00 um

Air Volume:19171Ut£rs Total Area Analyzed:0;0450 mm2 .

Filter Type: MCE 25 mm diam. Pore Size: 0.45 um Analytical Sensitivity: 22.2 s/mm2 Effective Area: 3 8 5 rnm2 0■0045 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct > = 5um Struct/mm2 Struct/cc ngm/m3

Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Amphibole Asbestos 0 0 0 Q 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0 Non-Asbestos 0 0 0 0 0 0 O.D 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 0.0000 N/A

Totals (All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty of this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type:■None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the -quality specified for the method.

Analyzed by: Report Reviewed by:

Marek Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CITY_21MC1OO_OO3O9927O

NYC-WTC_000270294

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000270294Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000293386

TEM asbestos analysis for Stuyvesant HS exterior site; sample 60357, opened 106.00 um.

Similar indexed content

NYC-WTC_000270518

TEM asbestos analysis with SAED/EDS for NSHS, exterior and interior areas, 10/17/01.

Similar indexed content

NYC-WTC_000293526

TEM asbestos analysis parameters for NSHS site, Oct 2001.

Similar indexed content

Compare copies and versions →