ATC EnvironmentalInc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/05/01

ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AKERA Final Rule. EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sample Identification Arial?zsisPa rameCe^

Pro j ect/Site: Stuwesant H.S., 34 5 Chambers St., NY, NY TEM Sample No,: 5609 - 60046 Floors 1-10 Date Received: 10/05/01 Grid Openings Analyzed:__ 4

Project Sample No.: SHS-l>10-lQ/5-39 Average Grid Opening: 106.00 urn

Air Volume: 18S3 liters Total Area Analyzed; 0.0450 mm2

Filter Type: MCE 25 mm diam., Pore Size: 0.45 um Analytical Sensitivity: 22.2 s/mm2 Effective Area: 385 mm2 0.0046 s/cc

FIBROUS PARTICULATES ANALYZED Humber Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct > = 5um Stiruct/nim2 Struct/cc ncTm/m3

Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0. 0 0.0000 0

Total asbestos {includes ambiguous structures) 0 0 0.0 0.0000 0 Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 d.OQOO N/A

Totals (All Structures) 0 "0 0.0 0.0000 N/A The estimated uncertainty of this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED) -. None detected Amphibole Asbestos Type: None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by: Report Reviewed by:

I Michael A. Gorycki, Ph.D. Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CITY_21MC1OO_OO3O99O57

NYC-WTC_000270119

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000270119Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000248305

TEM asbestos analysis for New Stuyvesant High School, received 10/27/01.

Similar indexed content

NYC-WTC_000270407

TEM analysis with SAED/EDS; exterior/interior building areas; 10/14/01.

Similar indexed content

Compare copies and versions →