NYC 9/11 Public Portal Document
NEW YORK CITY DEPARTMENT OF ENVIRONMENTAL PROTECTION
BUREAU OF WASTEWATER TREATMENT
LIMITATIONS FOR EFFLUENT DISCHARGE TO SANITARY OR COMBINED SEWERS
Project Name/Location WTC - South Projection Date; January 2,2001
Sample Treatment
Parameter Limitations Units Note Results * Over / Under Required
Temperature <150 DogF not measured
Total Petroleum Hydrocarbons 50 ppm 19.2 NO
eh 5-11 SU'S 8.09 NO
Cadmium 2 ppm Daily Avg. 0.69 ppm <0.05 NO
Chromium (total) 5 PP"* <0.05 NO
Copper 5 PP”* <0.06 NO
Lead 2 ppm <0.06 NO
Mercury 0.06 PPfi <0,002 NO
Nickel 3 ppm <0.05 NO
Zinc 5 ppm <0.05 NO
Flash Point >140 DegF >140 NO
Benzene 134 ppb Method 602 <5 NO
Ethylbenzene 380 £EL Method 6C2 <5 NO
Toluene 74 PP*’ Method 602 8 NO
Xylenes 74 ppb Method 602 <5 NO
EPa method 608 only with
PBC's (total) 1000 PPt MDL = 65ppt All below Detection Limit of 66 ppb
Total Suspended Solids No Limit 17 NO
iTetrachioroethyiene 164 ppb <5 NO
MTBE 10 ppb 66 SS YES
Napthalene 47 ppb <5 No
Other ppb
• Indicate test data origin Independent Testing Labs - College Point, NY - sample collected 12/13101
Grab sample from pump discharge
** Analysis for PCB’s are required ONLY if BOTH conditions listed below are met:
1) if proposed discharge > 10,000 gpd
2) if duration of a discharge >10 days