NYC 9/11 Public Portal Document
NEW YORK CITY DEPARTMENT OF ENVIRONMENTAL PROTECTION
BUREAU OF WASTEWATER TREATMENT
LIMITATIONS FOR EFFLUENT DISCHARGE TO SANITARY OR COMBINED SEWERS
Project Name/Location WTC - South Projection Date: January 2,2001
Sample Treatment
Parameter Limitations Units Note Results * Over / Under Required
Temperature <150 not measured
Total Petroleum Hydrocartwns 50 19.2 NO
pH 5-11 SU’s 8.09 NO
Cadmium 2 ppm Daily Avg. 0.69 ppm <0.05 NO
Chromium (total) 5 ppm <0.06 NO
Copper 5 PPn <0.05 NO
Lead 2 ppm <0.05 NO
Mercury 0.06 ppm <0.002 NO
Nickel 3 ppm <0.06 NO
Zinc 5 ppm <0.05 NO
Flash Point >140 DegF >140 NO
Benzene 134 PI* Method 602 <5 NO
Ethylbenzene 380 ppb Method 602 <5 NO
Toluene 74 PP*» Method 602 8 NO
Xylenes 74 PI* Method 602 <5 NO
EPA method 608 only with
PBC's (total) 1000 PP» MDL = 65ppt All below Detection Limit of 66 ppb
Total Suspended Solids No Umit 17 NO
Tetrachloroethylene 164 ppb <5 NO
MTBE 10 ppb 66 SS YES
Napthalene 47 PPi’ <5 No
Other PP^’
* Indicate test data origin Independent Testing Labs - College Point, NY - sample collected 12/1301
Grab sample from pump discharge
*• Analysis for PCB's are required ONLY if BOTH conditions listed below are met:
1) if proposed discharge > 10,000 gpd
2) if duration of a discharge > 10 days
CITY_2IMC16 0_0 0 303 7 311
NYC-WTC_000196022
OCR can misread numbers and units. Confirm readings against the page image before using them.