IAQ report, 90 Trinity Place, June 11, 2002

Machine-extracted title · confidence 41%

ATC IAQ measurements collected June 11, 2002 at the referenced school.

NYC-WTC_000260545–000260548
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Ori an June 12, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 * I'he measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Conceniration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During thi.s assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Thirteen (13) of the indoor measurements for temperature were above and none of the measurements were below the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and above rhe USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. 5. Two of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext #211 or 212.

Sincerely, Reviewed by; A TC ASSOCIA TES INC.

Q/ Yiannis Efstathidu James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CONFIDENTIAL, CITY_21MC100_003464625 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260548

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260548Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180220

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.

Similar indexed content

NYC-WTC_000410915

IAQ measurements at 90 Trinity Place; BOE requested assessment of air quality.

Similar indexed content

NYC-WTC_000410919

Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.

Similar indexed content

Compare copies and versions →