Mr. Bernard P. Ori an June 12, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

ReaL;J;ime Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The result.s are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 74.5 to 85.8 °F. Thirteen (13) of the indoor measurements for temperature were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 75.8 to 87.8 °F.

Relative Humidity

The relative humidity indoors ranged from 41.1 percent to 59.1 percent. All of the indoor measurements tor relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupart comfort. The outdoor relative humidity range was 58.2 to 65.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 563 ppm to 1410 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 523 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1223 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 37 pg/m^ with an average 20 pg/ni^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 128 pg/m^ to 280 pg/m^ with an average of 139 pg/m^.

CONFIDENTIAL, CITY_21MC100_003464624 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260547

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260547Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180220

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.

Similar indexed content

NYC-WTC_000410915

IAQ measurements at 90 Trinity Place; BOE requested assessment of air quality.

Similar indexed content

NYC-WTC_000410919

Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.

Similar indexed content

Compare copies and versions →