Mr. Bernard P. Ori an May 8, 2002
■ Indoor Air Quality Assessment Page 4
H.S. for Leadershit) & Public Service (M894) ATC Project No. 15-19125-0290
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the
AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building w as occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
I. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Thirty-one (31) of the indoor measurements for temperature were below and one (1) was
above the range of 73 to 79°F (at 50 percent relative humidity)
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. Five (5) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level.
5. All of the indoor and outdoor measurements for PM2.5 were within the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for
sensitive individuals such as asthmatic people and children.
It is our pleasure to provide these indoor air quality services to the New' York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or
212.
Sincerely,
,4 TC ASSOCIA TES INC.
Reviewed by:
Yiannis Efstatltiou James R. Cohn, CUL CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment