NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Leadership School, 90 Trinity Place

Machine-extracted title · confidence 42%

May 7, 2002; IAQ measurements for BOE program.

NYC-WTC_000260299–000260302
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Ori an May 8, 2002 ■ Indoor Air Quality Assessment Page 4 H.S. for Leadershit) & Public Service (M894) ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building w as occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

I. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Thirty-one (31) of the indoor measurements for temperature were below and one (1) was above the range of 73 to 79°F (at 50 percent relative humidity) 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. Five (5) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 5. All of the indoor and outdoor measurements for PM2.5 were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

It is our pleasure to provide these indoor air quality services to the New' York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or 212.

Sincerely, ,4 TC ASSOCIA TES INC. Reviewed by:

Yiannis Efstatltiou James R. Cohn, CUL CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003464207 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260302

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260302Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180220

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.

Similar indexed content

NYC-WTC_000260419

ATC provides indoor air quality measurements collected May 20, 2002.

Similar indexed content

NYC-WTC_000260303

May 8, 2002; IAQ measurements requested by BOE.

Similar indexed content

NYC-WTC_000260281

May 7, 2002 IAQ measurements; BOE requested testing.

Similar indexed content

Compare copies and versions →