Mr. Bernard P. Orlan May 28, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service fM894| ATC Project No. 15-19125-0290

Real-Time^ vironmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 72.6°F to 78.0°F. Two (2) of the indoor measurements for temperature were below and no readings were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 72.3 to 86.1 °F.

Relative Humidity

The relative humidity indoors ranged from 37.1 percent to 44.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 39.6 to 45.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 526 ppm to 1041 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 621 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1321 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 1 ppm for all collected readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was also 1 ppm for all readings.

Respirable Paniculates (PM2,s)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 20 pg/m^ with an average 12 pg/rn^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 31 pg/m^ to 40 pg/m^ with an average of 36 pg/m^.

CONFIDENTIAL, CITY_21MC100_003464426 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260489

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260489Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000410919

Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.

Similar indexed content

NYC-WTC_000410947

Follow-up IAQ report for the referenced NYC BOE project, June 2002.

Similar indexed content

NYC-WTC_000291976

ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.

Similar indexed content

Compare copies and versions →