Indoor air quality report, High School for Leadership, Jun 2002

Machine-extracted title · confidence 42%

ATC provides IAQ measurements conducted June 26, 2002 for the NYC BOE request.

NYC-WTC_000335309–000335312
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 27, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

Real-Time Et^viro^ental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperatiife

Indoor dry bulb temperature measurements ranged from 74.7 to 81.3 °F. Twenty-five (25) of the indoor measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 83.7 to 90.2 °F.

Relative Humidity

'fhe relative humidity indoors ranged from 44.8 percent to 61.3 percent. Two (2) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 51.4 to 80.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 631 ppm to 1126 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 653 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1353 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Montale ConcenHtatim

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm to 5 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 37 pg/m^ to 40 pg/m^ with an average 40 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/rn^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 248 pg/m^ to 459 pg/m^ with an average of 407 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_003058798

NYC-WTC_00033531 1

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335311Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292024

ATC IAQ measurements collected June 26, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000335305

ATC reports IAQ measurements conducted June 25, 2002 at the referenced NYC school.

Similar indexed content

NYC-WTC_000410955

ATC letterhead memo re IAQ measurements for H.S. Leadership, June 2002.

Similar indexed content

NYC-WTC_000410959

ATC memo reporting IAQ measurements for school in NYC BOE program, June 2002.

Similar indexed content

Compare copies and versions →