Mr. Bernard P. Orlan May 23, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 71.1 °F to 76.9 °F. Sixty-eight (68) of the indoor measurements for temperature were below and sixty (60) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature ranged from 64.8 to 71.6°F.

Relative Humidity

The relative humidity indoors ranged from 26.5 percent to 34.6 percent. One hundred and eight (108) of the indoor measurements for relative humidity were below and twenty (20) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 26.2 to 27.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 471 ppm to 1326 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration v/as 601 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1301 ppm (background level + 700 ppm). The highest reading (1326 ppm) was taken in room 306 at 1:53 PM with 30 occupants. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 1 ppm for all collected readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was also 1 ppm for all readings.

Respirable Pariiculates (PM2_ j)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 18 ug/m^ with an average 12 pg/rn-^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hou]- average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 40 pg/m^ to 51 pg/nC with an average of 46 pg/m^.

CONFIDENTIAL, CITY_21MC100_003464390 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260453

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260453Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000399272

May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.

Similar indexed content

NYC-WTC_000410919

Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.

Similar indexed content

Compare copies and versions →