Mr. Bernard P. Orlan May 21, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 64.2 °F to 75.1 °F. Thirty-six (36) of the indoor measurements for temperature was below and ninety'-two (92) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature ranged from 55.1 to 68°F.

Relative Humidity

The relative humidity indoors ranged from 23 percent to 42.1 percent. Seventy-one (71) of the indoor measurements for relative humidity were below and fifty-seven (57) were within the ASHRAE-recornmended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 19 to 27.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 577 ppm to 2861 ppm. Sixty-three (63) of the indoor measurements for CO2 were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 536 ppm. Therefore, the maximum acceptable level of CO? at this location was 1236 ppm (background level -r 700 ppm). The highest reading (2810 ppm) was taken in room 905 at 2:16 PM with 23 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NP.\AQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 1 ppm.

Resnirahle Paniculates (PM2,5)

Respirable particulate concentrations* indoors ranged between 1 pg/in^ to 63 pg/m^ with an average 20 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hou' average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred twenty-eight (128) instantaneous indoor measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 21 pg/m^ to 76 pg/m^ with an average of 40 pg/m3.

CONFIDENTIAL, CITY_21MC100_003464354 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260421

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260421Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000260451

Indoor air quality measurements taken May 22, 2002 for BOE.

Similar indexed content

NYC-WTC_000399254

Indoor air quality report dated May 7, 2002 for High School project; ATC.

Similar indexed content

Compare copies and versions →