Mr. Bernard P. Orlan May 21,2002 Indoor Air Quality .Assessment Page 4 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 * The measurements made during this assessment were instantaneous readings, the NTAAQS is a 24-hour average. TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline' for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Thirty-six (36) of the indoor measurements for temperature was below and ninety-two (92) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHR.AE Standard 55-1992 during the summer season. 3. Seventy-one (71) of the indoor measurements for relative humidity were below and fifty- seven (57) were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Sixty-three (63) of the indoor measurements for COg were above the ASHRAE Standard 62- 1999 recommended maximum concentration of <700 ppm above the background level. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the one hundred twenty-eight (128) instantaneous indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext. 211 or 212.

Sincerely, .4 TC ASSOCIA TES INC. Reviewed by:

lel JavAl j James R. Cohn, CIH, CSP Senior Privet Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003464355 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260422

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260422Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000260451

Indoor air quality measurements taken May 22, 2002 for BOE.

Similar indexed content

NYC-WTC_000399254

Indoor air quality report dated May 7, 2002 for High School project; ATC.

Similar indexed content

Compare copies and versions →