Mr. Bernard P. Orlan May 3, 2002 Indoor Air Quality Assessment Page 3 H.S. for LeadershiC' & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. B.eadings were collected in the morning and evening. The results are described below.
Temperature
Indoor dr)' bulb temperature measurements ranged from 64.6 °F to 76.3 °F. Eighty (80) of the indoor measurements for temperature were below and forty-eight (48) were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season . The outdoor temperature ranged from 59.8 to 69.3 °F.
Relative Humidity
The relative humidity indoors ranged from 42.4 percent to 56.7 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 43.0 to 59.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 496 ppm to 1589 ppm. One (1) of the indoor measurements for CO2 Was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 567 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1267 ppm (background level + 700 ppm). The highest measurement (1589 ppm) was collected in the (jymnasium around 10:55 A.M. with 13 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of avai lable outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonMon^de Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm These concentrations were below the NP.YAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from Ippm to 4ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 1 pg/nP to 55 pg/m^ with an average 19 pg/m3. Seven (7) of the outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter Five (5) of the indoor measurements and eleven (11) of the outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 39 pg/m^ to 158 pg/m^ with an average of 94 pg/m^.
CONFIDENTIAL, CITY_21MC100_003464152 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260247
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410927
Indoor air quality report for H.S. for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260451
Indoor air quality measurements taken May 22, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260347
ATC provides IAQ report for May 14, 2002 measurements at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399222
Indoor air quality measurements at the High School for Leadership & [name]; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399442
Indoor air quality measurements collected May 22, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291755
Indoor air quality measurements report for the school at 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260209
May 2002 IAQ measurements requested by BOE for the school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410931
IWQ measurements and narrative for H.S. Leadership project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260263
May 6, 2002 IAQ measurements for the school; BOE involvement.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260529
ATC IAQ measurements collected June 5, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291705
Indoor air quality report for High School for Leadership & [name], May 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394886
Indoor air quality measurements collected at the referenced school in April 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296893
Indoor air quality measurements at the referenced HS, BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399290
Indoor air quality measurements collected May 8, 2002, at the referenced school for BOE evaluation.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
Similar indexed content
NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
Similar indexed content
NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
Similar indexed content
Indoor air quality report for H.S. for Leadership & [name], June 2002.
Similar indexed content
Indoor air quality measurements taken May 22, 2002 for BOE.
Similar indexed content