IAQ measurement report, High School for Leadership, 90 Trinity Place

Machine-extracted title · confidence 42%

ATC report detailing IAQ measurements at the school; BOE requested testing.

NYC-WTC_000260150–000260153
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 25, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements

ATC collected one hundred and fifteen (115) sets of real-time environmental measurements consisting of one hiundred and three (103) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 7:32 A.M. and concluded at 6:00 PM. The results are described below.

Temperature

Indoor dry bull) temperature measurements ranged from 67.4 °F to 68.9 °F. All of the indoor measurements for temperature were below the range of 73°F to 79°F (at 50 percent relative humidity) recommcmded by ASHRAE Standard 55-1992 during the heating season (summertime conditions). Ilie outdoor temperature ranged from 68.2 to 68.9 °F.

Relative Humiditv

The relative humidity indoors ranged from 32.0 percent to 34.8 percent. All of the indoor measurements .for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 32.4 to 34.1 percent.

Carbon Dioxide Concentration

The CO, readings recorded were not considered to be accurate due to a suspected sensor problem. The COj sensor will be checked prior to the next use of this instrument.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm. These concentrations were below the NP.AAQS/ASHRAli guideline of 9 ppm. The outdoor CO concentrations were 0 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 6 pg/m^ with an average of 4pg<nri- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. None of the measurements were above the USEPA recommended concentration of 4C' pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 2 pg/m^ to 6 pg/m^ with an average of 4pg/m3. All of the outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24- hour average conc:entration of particulate matter 2.5 micrometers or less in aerodynamic diameter, and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

CONFIDENTIAL, CITY_21MC100_003464046 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260152

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260152Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394850

ATC IAQ report for High School for Leadership & [name], Trinity Place, April 2002.

Similar indexed content

NYC-WTC_000260419

ATC provides indoor air quality measurements collected May 20, 2002.

Similar indexed content

Compare copies and versions →