NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 1,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATCPrpiectNoM5H912S::0291

Real-Time Environmental Measurements

ATC collected one hundred forty-two (142) sets of real-time environmental measurements consisting of one hundred thirty-two (132) in the school building and nine (9) outdoors. Field data sheets are found in the Attachment. Readings began at 8:11 A.M. and concluded after 4:00 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 54.5 °F to 71.3 °F. One hundred twenty (120) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 32 to 57.6 °F.

Relative Humidity

The relative humidity indoors ranged from 16.8 percent to 36.3 percent. One hundred twenty- eight (128) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the ASHRAE recommended range. The outdoor relative humidity ranged from 17.5 to 24.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 321 ppm to 1168 ppm. One (1) of the measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 411 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1111 ppm (background level + 700 ppm). The highest reading was found in room 706 (1168 ppm) at 8:56 AM with 24 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 to 4 ppm. These concentrations were below the NPA.A.QS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 0 to 4 ppm.

Respirable Particulates (PM2^3)

Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 25 pg/m^ with an average 6 pg/m^ • None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The PM2.5 average concentration was also below the USEPA recommended concentration of 40 pg/m3 for sensitive individuals / children. The outdoor respirable particulate concentration ranged from 1 pg/m^ to 43 pg/m^ with an average of 26 ug/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL, CITY_21MC100_003461870 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259004

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259004Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000179968

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 1, 2002.

Similar indexed content

Compare copies and versions →