Memo: IAQ report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 42%

ATC memo reporting IAQ measurements at Stuyvesant High School, Jan 2002.

NYC-WTC_000255807–000255810
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • At the time of ATC’s site visit, room 125 was occupied by approximately 150 people.

FINDINGS

Based on the real-time measurements, the following findings are presented:-

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Twelve (12) CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Five (5) indoor measurements of relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other relative humidity measurements were below the ASHRAE-recommended range.

4. Twenty-three (23) temperature measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating ...L, season (wintertime conditions).

It is our pleasure to provide these indoor air quality services to the New York City Board of - Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, ' a /I TC ASSOCIA TES INC. Reviewed by: <7

Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

i

CONFIDENTIAL, CITY_21MC100_003457565 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255810

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255810Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311232

ATC report of IAQ measurements at Stuyvesant High School.

Similar indexed content

Compare copies and versions →