Mr. Bernard P. Orlan June 24, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M_____________________________ ATC Project No. 15-19125-0289 Re,\l-Time Envtroxmemai.vieasirf.mems
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 1:11 P.M. and concluded at approximately 2:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to 78.8 °F. Twelve (12) of the indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the mechanical cooling season (summertime conditions).The outdoor temperature measurements ranged from 82.1 °F to 84.1 °F.
Relative Humidity
Tlie relative humidity indoors ranged from 41.9 to 59.1 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 44.9 to 45.8 percent.
CqrbonDioxideConcenPtation
Carbon dioxide concentrations indoors ranged from 561 ppm to 1321 ppm. All of the CO2 indoor measurements were within the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 741 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1441 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. Tire school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 1 ppm for all collected readings. These concentrations were within the NPAAQS/ASHRAF guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all collected readings.
Respirable Particulates (PM2 5) ppm.
Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 31 pg/m3. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40pg'm- for sensitive individuals and children. The average PM2,5 concentration for the entire school building was approximately 24 pg/m^. The outdoor respirable particulate concentration measurements ranged from 50 to 59 pg/m^ with an average of 56 pg/m^.
CONFIDENTIAL, CITY_21MC100_005759993 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000250054
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000249964
Indoor air quality measurements at P.S. 150M to assess before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249976
Indoor air quality measurements taken at school site during June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250000
Indoor air quality measurements at PS 150M before occupancy recommencement.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253782
ATC IAQ measurements at PS150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249956
ATC IAQ measurements at P.S. 150M, prior to occupancy, BOE referenced.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253774
ATC IAQ measurements at PS 150M for pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374932
ATC IAQ measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249931
ATC IAQ measurements at PS 150M, May 31, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253831
Indoor air quality measurements at PS 150 for occupancy pre-reporting.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000398161
Indoor air quality measurements at P.S. 150M prior to re-occupancy; July 2002 addendum.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249964
Indoor air quality measurements at P.S. 150M to assess before re-occupancy.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374932
ATC IAQ measurements at school prior to re-occupancy.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178766
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 31, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250000
Indoor air quality measurements at PS 150M before occupancy recommencement.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253782
ATC IAQ measurements at PS150M prior to re-occupancy.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000249964
Indoor air quality measurements at P.S. 150M to assess before re-occupancy.
Similar indexed content
NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
Similar indexed content
NYC-WTC_000249976
Indoor air quality measurements taken at school site during June 2002.
Similar indexed content
NYC-WTC_000250000
Indoor air quality measurements at PS 150M before occupancy recommencement.
Similar indexed content
NYC-WTC_000250044
ATC letter presenting IAQ measurements taken before re-occupancy at a NYC school.
Similar indexed content