Mr. Bernard P. Orlan June 3, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M_________________________________ ATC Project No. 15-19125-0289
Real-Ti.me Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 1:10 P.M. and concluded at
approximately 2:20 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.9 °F to 79.6 °F. Six (6) of the indoor
measurements were above and four (4) measurements were below the range of 73 to 79°F (at 50
percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the
mechanical cooling season (summertime conditions). The outdoor temperature measurements
ranged from 85.6 °F to 86.1 °F.
Relative Humidity
The relative humidity indoors ranged from 38.3 to 48.1 percent. All of the measurements were
within the ASIIRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 52.0 to 52.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 626 ppm to 1109 ppm. All of the CO2
indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 601 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1301 ppm (background level -t- 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations was 1 ppm for all collected readings. These
concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentrations was 1 ppm for all collected readings.
Respirable Particulates (PM2,j) ppm.
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 22 pg/m^. None of
the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA
recommendation of 40pg/m3 for sensitive individuals and children. The average PM2,5
concentration for the entire school building was approximately 14 pg/m^. The outdoor
respirable particulate concentration measurements ranged from 22 to 26 pg/m^ with an average
of 25 pg/m3.