NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 28, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M______________________________ ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69 °F to 73.2 °F. Twenty-seven (27) of
the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season
(summertime conditions). The outdoor temperature measurements ranged from 66°F to 67.9°F.
Relative Humidity
The relative humidity indoors ranged from 41.3 to 48.7 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 44 to 45 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 610 ppm to 1240 ppm. One (1) of the CO2
measurements was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 516 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1216 ppm (background level -t- 700 ppm). The highest level was recorded in the
music room at 1:00 PM with 25 occupants. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside
makeup air. The primary source of CO2 indoors is occupant respiration. The school building
was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 1 ppm for all collected readings. These
concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentration were 1 ppm for all collected readings.
Respirable Particulates (PM2,5) ppm.
Respirable particulate concentrations* indoors ranged between 20 pg/m^ to 38 pg/m\ None of
the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA
recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5
concentration for the entire school building was approximately 32 pg/m^. The outdoor
respirable particulate concentration measurements ranged from 80 to 90 pg/m^ with an average
of 86 pg/m^.