NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, June 24/25, 2002

Machine-extracted title · confidence 41%

Indoor air quality measurements at P.S. 150M prior to re-occupancy; July 2002 addendum.

NYC-WTC_000398161–000398164
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M_________________________________ ATC Project No. 15-19125-0289 Real-Time Environmental Mea^rements

ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 1:10 P.M. and concluded at approximately 2:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 72.3 °F to 76.2 °F. Three (3) of the indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions).The outdoor temperature measurements ranged from 86.9 °F to 87.8 °F.

Relative Humidity

The relative humidity indoors ranged from 49.1 to 54.3 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 49.0 to 50.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 561 ppm to 1184 ppm. All of the CO2 indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 778 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1448 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monp^eConcentration

Carbon monoxide indoor concentrations were 1 ppm for all collected readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all collected readings.

Respirable Particulates (PM2_j) ppm.

Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 36 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 25 pg/m^. The outdoor respirable particulate concentration measurements ranged from 59 to 76 pg/m^ with an average of 69 pg/m3.

CITY_21MC100_002894329

NYC-WTC_000398163

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000398163Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →