NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

Asbestos TEM analysis, Nev. Stuyvesant H.S., Oct 2001

Machine-extracted title · confidence 58%

TEM-based asbestos analysis with SAED/EDS for New Stuyvesant High School, Oct 2001.

NYC-WTC_000244598
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/18/01

ASBESTOS FIBER JiNALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fibe:r Identification oy Selected-Area Electron Diffraction ^SAEDi and Energy-Dispersive X-RAY Spectroscoov (EDS, Method: AHERA Final Rule, EPA Federal Register (40 CFR, Part 763). Vol. 52, No. 210, October 30, 1987

Sample 7den^icicarion Analysis Parameters

Project/Site: New .?tu\czesan- S., 345 Chambers St., NY, NY TEM Samuie No.: 5725 €1636 Ex re. ri ef Buildinq t Rocf Date Received: 10/lB/cl Grid Openings Analyzed;__ 4

Project Sample No.: 04 Average Grid Opening :J^££^00 um

Air Velum® ; 1928 1Lte^ Total Area Tmalyzed: 0.O4SC mm2

Filter Type: MCE 25 mm diam. Pore Size: 0.45 urn Analytical Sensitivity: 22.2 s/mm2 Effective AreE : 385 mm2 0044 s/cc

FIBROUS PARTICULATES /ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct, struct > = 5um Struct/mm2 Struct/cc nam/m3

Chrysotile Asbestos C 0 0 0 0 0 0. 0 0.0000 0

Amphibole Asbestos G 0 c 0 0 0 0.c 0.0000 0

Ambiguous C 0 0 0 0 0 0.c C.0000

Total asbestos (includes ambiguous structures) 0 0 0 .C 0.0000 C Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 0.0000 N/A

Totals (All Structures'; 0 0 0.0 0.0000 N/A The estimated uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbesto,s Type: None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by: Report Reviewed by:

Michael A. Gcrycki, Ph.D. Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CONFIDENTIAL, CITY_21MC100_003470120 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000244598

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000244598Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000244635

TEM asbestos analysis of samples from inside/outside New Stuyvesant HS.

Similar indexed content