Mr. Bernard P. Orlan August 29, 2002
Indoor Air Quality Assessment Page 4
P.S. 126M&M893 ATC Project No. 15-19125-0343
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
No TVOCs were detected indoors. The AIHA guideline for odor control is 1 ppm. The outdoor
TVOC concentration was'0.0 ppm.
OBSERVATIONS
• During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• People observed in only few rooms in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO and TVOCs were within applicable standards and guidelines.
2. Nine (9) of the indoor temperature measurements were above the range of 73 to79 °F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer
I
season. ASHRAE standard does not apply directly to a naturally-ventilated building.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. All of the indoor measurement for PM2.5 were within the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
It is our pleasure to provide these indoor air quality services to the New York City Department of
Education. If you have any questions about this report, please call (212) 353-8280, extension 370
or212.
Sincerely,
A TC ASSOCIA TES LNC.
Reviewed By:
James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment