Mr. Bernard P. Orlan September 6, 2002
Indoor Air Quality Assessment Page 4
P.S. 42 M ATC ProiectNo. 15-19125-0342
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs concentrations indoors ranged from 0 ppm to 0.8 ppm. The AIHA guideline for odor
control is 1 ppm. The outdoor TVOC concentrations were 1,0 ppm and 1,6 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was construction going on outside the building;
• The building has no central A/C;
• People observed in only few rooms in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of CO2, CO and TVOCs were within applicable standards and guidelines.
2. Nine (9) of the indoor temperature measurements were above the range of 73 to79 ’F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer
season. ASHRAE standards do not apply directly to a naturally-ventilated building.
3. Thirty-eight (38) of the indoor measurements for relative humidity were above the
ASHRAE-recommended range of 30 to 60 percent for occupant comfort.
4. All of the indoor measurements for PM2,5 were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children
and above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter. At the time of ATC’s site visit there was
construction going on outside the building, also the sensitivity of the Dust Trak® to high
humidity may have influenced these results;
5. One of the outdoor TVOC,s measurement was above the AIHA guideline for odor control is
1 ppm.
It is our pleasure to provide these indoor air quality services to the New York City Department of
Education. If you have any questions about this report, please call (212) 353-8280, extension 211
or 212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed By:
Yiannis Efstathiou James R, Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment