Mr. Bernard P. Orlan August 29, 2002
Indoor Air Quality Assessment Page 3
P.S. 126M & M893 ATCProiectNpU5U^125;^^
Real-Time Environmental Measurements
ATC collected seventy (70) sets of real-time environmental measurements consisting of sixty
eight (68) in the school building and two (2) outdoors. All floors of the school were surveyed.
Field data sheets are found in the Attachment. Readings were collected during school hours. The
results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from. 74.0 to 80.5 °F. , Nine (9) of the indoor
measurements were above the range of 73 to 79 °F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor
temperature measurements were 70.8 and 72.0 °F.
Relative Humidity
The relative humidity indoors ranged from 36.1 percent to 42.6 percent. All of the indoor
. measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity measurements were 50.1 and 51.8
percent collected before and after the indoor samples.
1
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 424 ppm to 851 ppm. All indoor
measurement for CO2 were within the ASHRAE Standard 62-2001 recommended maximum
concentration of <700 ppm above the background level. The average outdoor (background) CO2
concentration was 450 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1150 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an
indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CaripnMonm^e Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The average outdoor CO
concentrations was 1 ppm. .
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 15 pg/m^. All of
indoor measurements collected were within the USEPA recommended concentration of 40
pg/m3 for sensitive individuals such as asthmatic people and children. The two outdoor
respirable particulate concentrations were 11 pg/m^ and 13 pg/m^ with an average of 12 pg/m^.
USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic
people and children.