Indoor air quality report letter, P.S. 126M, Aug 2002

Machine-extracted title · confidence 95%

Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 126M on August 28, 2002.

NYC-WTC_000239058–000239061
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan August 29, 2002 Indoor Air Quality Assessment Page 3 P.S. 126M & M893 ATCProiectNpU5U^125;^^

Real-Time Environmental Measurements

ATC collected seventy (70) sets of real-time environmental measurements consisting of sixty­ eight (68) in the school building and two (2) outdoors. All floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected during school hours. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from. 74.0 to 80.5 °F. , Nine (9) of the indoor measurements were above the range of 73 to 79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements were 70.8 and 72.0 °F.

Relative Humidity

The relative humidity indoors ranged from 36.1 percent to 42.6 percent. All of the indoor . measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 50.1 and 51.8 percent collected before and after the indoor samples. 1 Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 424 ppm to 851 ppm. All indoor measurement for CO2 were within the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level. The average outdoor (background) CO2 concentration was 450 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1150 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CaripnMonm^e Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The average outdoor CO concentrations was 1 ppm. .

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 15 pg/m^. All of indoor measurements collected were within the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The two outdoor respirable particulate concentrations were 11 pg/m^ and 13 pg/m^ with an average of 12 pg/m^.

USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.

CONFIDENTIAL, CITY_2IMCl00_003421880 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000239060

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000239060Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →