Asbestos air sampling report summary, 40 Rector Street, Oct 2001

Machine-extracted title · confidence 95%

Summary report of asbestos air sample results for floors one through nineteen at 40 Rector Street.

NYC-WTC_000237582
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/n Public Portal Document * UCJ W FK I HMNtnaHUn-f-ltLI-tKM IRlOaUUUbUfa TO 5451405 P.03/05

4-^ 104 Hast 25tn Street Mew Yorir, New York W O ww/,3tc-ef'.viro,5o.^ 212353,5?.e0 F.3X 212.353 330® associates INC.

VIA FACSIMILE; 212-371-1084

October 1, 2001

40 RECTOR HOLDINGS. LLC c/o TANNEN3AUM HELPERN SYRACUSE & HIRSCHTRITT LLP 900 Third Avenue New York, New York 10022-4775 Attn; Mr. Scott Furman

RE: Ambient Air Sampling 40 RECTOR STREET, New York

Dear Mr, Furman; ATC Associates Inc, (ATC) is pleased to submit this summary report presenting the asbestos air sample results for the first through nineteenth floors of 40 Rector Street. Between September 20 and 28, 2001, ATC collected five ambient air samples per floor, totaling 90 samples to ascertain the presence or absence of airborne asbestos, within the subject facility. All samples coliected were analyzed in accordance with the AHERA Transmission Electron Microscopy (TEM) method as set forth at 40 CFR Part 763, Subpart E, Appendix A. Acceptable ambient air samples results are those sample sets meeting the AHERA re-occupancy requirement following an asbestos abatement action of an average of less than 70 asbestos structures per square millimeter {^70 s/mm®). Summary of Ambient Air Sample Results for 40 Rector Street Floor Analy^cal Result Floor Analytical Result 1 No structures detected 10 All samples <70 s/mm^ 2 All samples <70 s/mm^ 11 All samples <70 s/mm^ 3 All samples <70 s/mm® 12 All samples <70 s/mm’ 4 All samples <70 s/mm^ 14 All samples <70 s/mm® 6 Sample set average 23 s/mm^ 15 All samples <70 s/mm’ 6 AH samples <70 s/mm^ 16 No Structures detected 7 AH samples <70 s/mm’ 17 All samples <70 s/mm’ 8 All samples <70 s/mm^____ _ 18 All samples <70 s/mm’ 9 All samples <70 s/mm^ 19 All samples <70 s/mm^

Based upon the analytical results within the AHERA clearance requirement, it is ATC’s opinion that the ambient air samples collected throughout the building rneet an acceptable criterion for re-occupancy. If you have any questions or require additional explaination of the information presented please do not hesitate to call me al 212-353-8280 Sincerely,

Fred Burkhardt Senior Project Manager ATC Associates Inc.

CONFIDENTIAL INSURANCE INFORMATION, CITY_21MC100_013507976 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 NYC-WTC_000237582

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000237582Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000291213

AS asbestos air sample results for first-to-nineteenth floors; summary report.

Similar indexed content

Compare copies and versions →