Mr. Bernard P. Orlan January 25, 2002 Indoor Air Quality Assessment Page 3 P. S.89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- four (74) from inside theschool building and six (6) outdoors. All five floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 2:05 P.M.

Temperatio-e

Indoor dry bulb temperature measurements ranged from 62.0 °F to 72.5 °F. Seventeen (17) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASIIRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 50.0 to 53.9 °F.

Relative Humidity

The relative humidity indoors ranged from 37.0 percent to 66.7 percent. Three (3) measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 56.7 to 66.4 percent.

Carbon Dioxide Concenlration

Carbon dioxide concentrations indoors ranged from 488 ppm to 534 ppm. One (1) COn measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations ranged from 488 to 534 ppm. Therefore, the maximum acceptable level of CO2 ar this location was 1234 ppm (background level -t- 700 ppm). The highest CO2 reading was found in room 402. At the time of ATC’s assessment, this room was occupied by approximately thirty (30) people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COn indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm.

Respirable Particulates CPM2^§}

Respirable particulate concentrations* indoors ranged between 21 pg/m^ to 63 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2,5 concentration for the entire school building was approximately 42 pg/m3. This average

CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014659928

NYC-WTC_000236942

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000236942Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →