Mr. Bernard P. Orlan May 14, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Proiect No. 15-19125-0289
J
Real-Time Environmental measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 59.7°F to 70.6°F. All of the
measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season
(summertime conditions). The outdoor temperature measurements ranged from 56.2°F to
57.3°F.
Relative Humidity
The relative humidity indoors ranged from 50.9 to 76.0 percent. Eleven (11) of the
measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity measurements ranged from 62.1 to 64.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 556 ppm to 1136 ppm. One (1) of the CO2
measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration
of <700 ppm above the background level. The maximum outdoor (background) CO2
concentration was 396 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1096 ppm (background level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside
makeup air. The primary source of CO2 indoors is occupant respiration. The school building
was occupied during ATC’s assessment.
CqrbpnMonpxideQjncentration
Carbon monoxide indoor concentrations ranged from 0 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were 0
ppm for all collected readings.
Respirable Particulates (PM2,s) ppm.
Respirable particulate concentrations* indoors ranged between 17 pg/m3 to 52 pg/m-V None of
the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter. Nine (9) of the indoor
readings were above the USEPA recommendation of 40pg/m3 for sensitive individuals and
children. The average PM2.5 concentration for the entire school building was approximately 37