NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 14, 2002
Indoor Air Quality Assessment Page 4
P.S. 150M ATC Project No. 15-19125-0289
pg/m^. The outdoor respirable particulate concentration measurements ranged from 50 to 60
pg/m3 with an average of 55 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, and TVOCs were within applicable standards and guidelines;
2, All temperature measurements were below the range of 73 to 79° F (at 50 percent relative
humidity recommended by ASHRAE Standard 55-1992 during the mechanical cooling
season (summertime conditions).
3. Eleven (11) measurements of relative humidity were above the ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
4. One (1) CO2 measurement was above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level.
5. Nine (9) of the indoor and all of the outdoor respirable particulate readings were above the
USEPA recommendation of 40pg/m3 for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.
Sincerely, Reviewed by:
TC ASSOC/A TES INC.
Yiannis Efstathiou James R, Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_002870559
NYC-WTC_000214385
OCR can misread numbers and units. Confirm readings against the page image before using them.