Mr. Bernard P. Orlan June 20, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Proiect No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:00 A.M.

Temperalure

Indoor dry bulb temperature measurements ranged from 68.4 °F to 72.6 °F. All of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 69.1 °F to 69.2 °F.

RelatiyeHumiiiity

'Fhe relative humidity indoors ranged from 53.9 to 59.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 65.1 to 65.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 561 ppm to 1261 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 588 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1288 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were 2 ppm for all collected readings.

Respirable Particulates (PM2^ s)

Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 35 pg/m^. The average PM2,5 concentration for the entire school building was approximately 23 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The

CITY_21MC100_002863447

NYC-WTC_000211038

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000211038Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →