5.10 HVAC System
The HVAC system was cleaned in two of the commercial units. The system was cleaned by
professionals using equipment and techniques common to the industry that included HEPA-
filtered vacuums, air whips, air washing and soap and water washes. Wipe samples were
I* collected prior to cleaning and after cleaning for comparison. The results indicate that overall
there was a reduction of an order of magnitude for the compounds which were detected. In The
Food Exchange, lead was reduced from 1,310 pg/m’ to 159 pg/m^ (average), MMVF was
reduced from 11,732 S/cm^ to<57.3 S/cm^. In the Lemongrass Grill, there was a reduction in
w lead concentrations from 10,700 pg/m’ to 95.95 pg/m’ (average). This indicates that standard
HVAC cleaning methods and equipment reduced the concentrations of WTC-related
contaminants by an order of magnitude.