104 East 25th St., 10th Floor New York. New York 10010 ivwwatc-enviro.com 212.353.828C Fa> 212.353.8306 ASSOCIATES INC.

June 17,2002

Mr. Bernard P. Orlan Director, Environmental Health & Safety Nev/ York City Board of Education 28- 1 Queens Plaza North Long Island City, NY 11101-4008

Re: Indoor Air Quality Assessment High School of Economics and Finance (M833) 100 Trinity Place New York, New York 10006 ATC Project No. 15-19125-0291

Des r Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on June 14, 2002 at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.

SCOPE OF WORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carcon dioxide (COj) and carbon monoxide (CO).

To- al volatile organic compounds (TVOCs) and respirable particulates were also measured.

Jimmy Choy, Environmental Technician of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual Inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured temperature, relative humidity, CO, and CO with a Q-Trak* Model 8551, mrnufactured by TSI, Inc.

A”C measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® AerC'Sol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.

CONFIDENTIAL, CITY_21MC100_003462883 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000180089

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000180089Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180019

Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 10, 2002.

Similar indexed content

NYC-WTC_000180015

Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.

Similar indexed content

NYC-WTC_000180045

Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.

Similar indexed content

Compare copies and versions →