NYC 9/11 Public Portal Document
A r. Bernard P. Orlan June 17, 2C02
Ir door Air Quality Assessment Page 2
H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
Tae results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times. The information presented in this report should be used
by the BOE as a guide to assess the need for further improvements in current indoor air quality
control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications;
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
lable 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
v'ill be achieved at all times.
TABLE 1
3 ARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL
Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62
above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
.ICO)__________ USEPA NPAAQS)____________
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM25) of air (ug/n?) 24-hour average
40 |ig/m’ 24-hour average USEPA - Recommendation for
children / sensitive individuals
Temperature Summer; 73-79°F at 50% RH ASHRAE 55
Winter; 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile Organic
Compounds (TVOC) 1 ppm AIHA
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_003462884
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000180090