NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 17,2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Project No. 15-19125-0289
t
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.7°F to 75.4°F. Two (2) of the
measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season
(summertime conditions). The outdoor temperature measurements ranged from 72.8°F to
74.6°F.
Relative Humidity
The relative humidity indoors ranged from 30.9 to 37 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 20 to 22.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 513 ppm to 1130 ppm. One (1) of the CO2
measurements was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 401 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1101 ppm (background level + 700 ppm). The highest reading (1130 ppm) was
taken by the slop sink area in the hallway at 1:00 PM. Levels above the recommended maximum
do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outside makeup air. The primary source of CO2 indoors is occupant respiration. The school
building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2
ppm for all collected readings.
Respirable Particulates (PM2,5) ppm.
Respirable particulate concentrations* indoors ranged between 12 pg/m^ to 35 pg/m^. None of
the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5
concentration for the entire school building was approximately 23 pg/m^. The outdoor