Mr. Bernard P. Orlan May 3,2002
Indoor Air Quality Assessment Pages
P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.6°F to 73.8°F. Twenty-three (23) of
the measurements were below the range of 73 to 79®F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the heating season (summertime
conditions). The outdoor temperature measurements ranged from 51.6°F to 53.3°F.
Relative Humidity
The relative humidity indoors ranged from 30.1 to 48.8 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 45.0 to 47.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 669 ppm to 1002 ppm. All of the CO2
measurements were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 484 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1184 ppm (background level -f- 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 1 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were also 1
ppm for all collected readings.
Respirable Particulates (PM2_5) ppm.
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 23 pg/m^. None of
the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA
recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5
concentration for the entire school building was approximately 15 pg/m^. The outdoor
respirable particulate concentration measurements ranged from 25 to 30 pg/m3 with an average
of 27 pg/m3.